Products
SCB-1250kVA H Class Three Phase Dry-Type Transformer
video
SCB-1250kVA H Class Three Phase Dry-Type Transformer

SCB-1250kVA H Class Three Phase Dry-Type Transformer

The SCB-1250kVA H class three phase dry-type transformer launched by TRANSpower ELECTRICAL strictly complies with international standards and has proven its excellent performance and reliability with more than ten years of trouble-free operation. Its large capacity, high efficiency and low noise characteristics are widely used in large industrial plants, commercial centers and other places with high power demand.

Transpower Electrical Equipment Co., Ltd. is one of the most reliable manufacturers and suppliers of scb-1250kva h class three phase dry-type transformer in China. Welcome to buy high quality customized products at competitive price from our factory. Contact us for quotation.

 

SCB-1250kVA H Class Three Phase Dry-Type Transformer

 

The SCB-1250kVA H class three phase dry-type transformer launched by TRANSpower ELECTRICAL strictly complies with international standards and has proven its excellent performance and reliability with more than ten years of trouble-free operation. Its large capacity, high efficiency and low noise characteristics are widely used in large industrial plants, commercial centers and other places with high power demand.

 

Products Description

 

info-606-704

SCB-1250kVA H class three phase dry-type transformer is a high-performance power equipment designed for occasions requiring large-capacity power supply. Its 1250kVA rated capacity and H-class insulation level enable it to withstand high loads and harsh working environments, ensuring the stable operation of the power system.

The internal structure of the transformer adopts advanced design concepts to ensure efficient energy conversion and low loss. High-strength insulation materials are used between the three-phase coils and between the coils and the core to improve the electrical safety performance of the transformer. At the same time, the transformer is also equipped with an efficient heat dissipation system and a complete protection system to ensure stable operating temperature and equipment safety even under long-term high-load operation.

info-603-601
info-713-616

It is widely used in large-scale industrial production lines, commercial complexes, data centers and other occasions requiring large-capacity power supply. With its excellent performance and reliable quality, SCB-1250kVA H class three phase dry-type transformer provides a strong guarantee for the power demand of these occasions.

 

SCB Three Phase Dry-Type Transformer

 

Industry-specific attributes

Product

SCB Three Phase Dry-Type Transformer

Phase

Three

Coil Structure

Toroidal

Coil Number

Double winding

Other attributes

Place of Origin

Zhejiang, China

Model Number

Three phase SCB Dry-Type Transformer (As per customer requirements)

Rated capacity

From 30kva to 2500kva

High Voltage

6kV and 38.5kV

Low Voltage

0.4kV

Frequency

50/60Hz

Standard

IEC, ANSI, IEEE, CSA

Vector group

Dyn11, Yyn0

Material

Aluminum/Copper

Application

Industrial plants, data centers, residential buildings, hospitals, and commercial complexes

Type

Oil-immersed Transformer

Feature

Maintenance-free, suitable for indoor installations, resistant to moisture, and environmentally friendly due to their lack of oil

 

product-778-644

 

SCB Dry-Type Transformer parameters

 

The following table is the standard parameter of the SCB Dry-Type Transformer. If you need other capacity and voltage levels, please contact the TRANSpower to obtain accurate technical parameters and offers.

Below Specs Are ONLY For Reference.

CAPACITY
(kVA)

Voltage ratio and tap range (kV)

Connection Symbol

13Type Loss (W)

Impedance

(%)

No-load current

HV

LV

No-load loss (kW)

Full-load loss

(kW)

30

35

38.5

±5%

or

±2

x2.5%

0.4

Dyn11

or

Yyn0

360

1220

6

2.8

50

450

1520

2.6

80

540

1930

2.2

100

630

2235

2

125

700

2590

1.8

160

790

3010

1.8

200

880

3565

1.6

250

990

4065

1.6

315

1175

4825

1.4

400

1375

5775

1.4

500

1620

7080

1.4

630

1860

8265

1.2

800

2160

9740

1.2

1000

2430

11210

1

1250

2835

13585

1

1600

3240

16530

0.8

2000

3825

19475

0.7

2500

4455

23370

0.7

 

info-794-586

315kVA 13.2kV Three Phase SCB Dry-Type Transformer dimensions and weight details

 

info-600-460
info-600-460

 

Frequently asked questions (FAQ)

 

Q: What is the IEC standard for dry type transformer?

A: IEC 60076-11:2018 applies to dry-type power transformers (including auto-transformers) having values of highest voltage for equipment up to and including 72,5 kV and at least one winding operating at greater than 1,1 kV.

Q: How do you check the temperature of a transformer?

A: The winding temperature is measured by a thermometer with any type of sensor, for dry type and cast resin transformers a Pt100 platinum probe is usually used. Fibre optics, infrared sensors or thermocouples can be used for different temperature measurements in different types of transformers.

Q: What is the safe temperature for a transformer?

A: The average ambient temperature of the transformer over a 24 hour period should not exceed 30 degrees Celsius. For example, if the ambient temperature of the transformer is 40 degrees Celsius for 12 hours, the temperature of the transformer shall not exceed 20 degrees Celsius for the remaining 12 hours, with an average temperature of 30 degrees Celsius.

 

Hot Tags: scb-1250kva h class three phase dry-type transformer, China scb-1250kva h class three phase dry-type transformer manufacturers, suppliers, factory, SCB13 Three Phase Dry-type Power Transformer, power distribution equipment transformer, transformer housing, SCB Series Epoxy Resin Dry Type Transformer, transformer panel, cast resin transformer

Send Inquiry